What Are Some Battery Maintenance and Storage Tips for my Best Technologies Micro-FERRUPS FE1.4KVA Unit. The proper storage of your Best Technologies Micro-FERRUPS FE1.4KVA batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse. All batteries exhibit a loss of charge over time even when stored in an open circuit condition. This is called self-discharge. Both chemical and electrochemical reactions within the battery cause this consumption of the stored energy. The self-discharge reaction rate increases as a function of temperature. If the batteries are stored long enough without a periodic replenishment of charge, an irreversible loss of battery capacity can occur, causing premature battery failure.
Best Technologies Micro-FERRUPS FE1.4KVA should be stored separately from the UPS and used according from oldest to newest. All Best Technologies Micro-FERRUPS FE1.4KVA battery packs should be recharged before use if 100% capacity is required. The stored Best Technologies Micro-FERRUPS FE1.4KVA battery should be kept on a maintenance program and should be recharged periodically according to the recommendations of the tabel below. Battery packs can be recharged using the Best Technologies Micro-FERRUPS FE1.4KVA UPS unit.
Storage Temperature / Recharge Intervals Below 20°C (68°F) / Every six months Between 20°C and 30°C (68°F and 86°F) / Every three months Over 30°C (86°F) / Storage to be avoided